Modbus TCP

The modbus probe polls Modbus TCP Holding Registers on PLCs, industrial sensors, and smart-building controllers. Each configured register becomes one metric with a name and unit you define. Supports uint16, int16, uint32, int32, float32_abcd and float32_cdab register types.

Quick start

probes:
  - name: modbus-plc
    type: modbus
    params:
      host: 192.168.1.100
      registers:
        - name: temperature
          address: 40001
          type: float32_abcd
          scale: 0.1
          unit: Cel
          description: Room temperature

Parameters

Parameter Default Description
host required IP address or hostname of the Modbus TCP device
port 502 Modbus TCP port
unit_id 1 Modbus unit (slave) ID
registers required List of register definitions (see below)

Register definition

Field Description
name Register name — becomes the register.name tag and PRTG channel name
address Modicon 1-based holding-register address (e.g. 40001)
type Data type: uint16, int16, uint32, int32, float32_abcd, float32_cdab
scale Multiplier applied after decoding (default 1.0)
unit OTel unit string for the value (e.g. Cel, %, 1)
description Human-readable label

Metrics

Metric Unit Description
modbus.register.value configurable Decoded register value, tagged with register.name and register.address
modbus.up 1 1 when the Modbus TCP device answered all register reads this cycle

Operational notes

  • host is required; the probe will fail to start without it.
  • Address numbering follows the Modicon 1-based convention (40001 = holding register 0). Subtract 40001 to get the 0-based Modbus Protocol Data Unit address if needed.
  • For float32_abcd vs float32_cdab, check your device manual for the byte-word order it uses.