Modbus TCP

The modbus probe polls Modbus TCP Holding Registers on PLCs, industrial sensors, and smart-building controllers. Each configured register becomes one metric with a name and unit you define. Supports uint16, int16, uint32, int32, float32_abcd and float32_cdab register types.

Quick start

# probes.d/20-modbus.yaml — each file under probes.d/ is a YAML array of probes
- name: modbus-plc
  type: modbus
  params:
    host: 192.168.1.100
    registers:
      - name: temperature
        address: 40001
        type: float32_abcd
        scale: 0.1
        unit: Cel
        description: Room temperature

Parameters

Parameter Must set Default Description
host Yes - Device address or hostname. Example: 192.168.1.100
port No 502 Modbus TCP port
unit_id No 1 Modbus unit (slave) identifier
timeout No 10s Per-read timeout, seconds or a duration
interval No 30 Seconds between collections
registers Yes - Registers to read and how to decode them
registers[].name Yes - Register name, the register.name attribute of the value
registers[].address Yes - Holding-register address, Modicon 1-based (40001) or 0-based on non-standard devices
registers[].type Yes - How the raw bytes are decoded. One of uint16, int16, uint32, int32, float32_abcd, float32_cdab
registers[].scale No 1 Multiplier applied after decoding; 0 counts as 1
registers[].unit No 1 OTel unit of the value. Example: Cel
registers[].description No - Human-readable label for dashboards

A register's name is also the PRTG channel name of its value.

Metrics

Metric Unit Description
modbus.register.value configurable Decoded register value, tagged with register.name and register.address
modbus.up 1 1 when the Modbus TCP device answered all register reads this cycle

Operational notes

  • host is required; the probe will fail to start without it.
  • Address numbering follows the Modicon 1-based convention (40001 = holding register 0). Subtract 40001 to get the 0-based Modbus Protocol Data Unit address if needed.
  • For float32_abcd vs float32_cdab, check your device manual for the byte-word order it uses.

Metric reference

Every metric this probe can emit. Metric is the OpenTelemetry name the OTLP, Prometheus and Zabbix outputs derive theirs from. Name is what a Nagios check and the API metrics= filter match. PRTG channel is the label PRTG shows, placeholders filled from the series' tags.

Metric Name PRTG channel Unit Description
modbus.register.value modbus.register.value Register 1 Decoded value of the Modbus Holding Register
modbus.up modbus.up Modbus Device Up # 1 when the Modbus TCP device answered all register reads in the last cycle